#42 Marcela St., Damong Maliit, Brgy. Nagkaisang Nayon, Novaliches, Quezon City 1125, Metro Manila, Philippines
NOJA OSM Three Phase automatic circuit reclosers are designed for use on overhead distribution lines as well as distribution substation applications for all voltage classes up to 38kV.
The product is supplied complete with an RC control and communications cubicle. The RC control cubicle provides all the protection, data logging and communications functions in a single device. The OSM has been designed for use as a stand-alone device that is easily integrated into distribution automation and remote control schemes using the in-built communications capability.
The product has been extensively type tested by independent laboratories to ensure long life and reliability under the harshest environmental conditions. The OSM automatic circuit recloser is the only solid di-electric insulated recloser to provide controlled arc fault venting and the independent testing provides verification of this important safety feature.
For more info visit website: www.nojapower.com.au
Part Number | OSM15-16-800 | OSM27-12-800 | OSM38-12-800 | OSM38-16-800 |
Manufacturing model | 311//312/310 | 311/312/310 | 311/302/300 | 301/302/300 |
Current Sensing | 3 x Current Transformers | 3 x Current Transformers | 3 x Current Transformers | 3 x Current Transformers |
Voltage sensing |
6 x Voltage Screens | 6 x Voltage Screens | 6 x Voltage Screens | 6 x Voltage Screens |
Rated Maximum Voltage | 15.5kv | 27kV | 38kV | 38kV |
Rated Continous Current | 800A | 800A | 800A | 800A |
Fault Make Capacity RMS | 16kA | 12.5kA | 12.5kA | 16kA |
Fault Make Capacity PEAK | 40kA | 31.5kA | 31.5kA | 40kA |
Fault Break Capacity | 16kA | 12.5kA | 12.5kA | 16kA |
Mechanical / Full load Operations | 30,000 | 30,000 | 30,000 | 30,000 |
Fault Break Capacity Operations | 70 | 70 | 70 | 70 |
Short Time Current Withstand | 16kA/3 secs | 16kA/3 secs | 12.5kA/3secs | 16kA/3 secs |
Mainly Active Breaking Capacity | 800A | 800A | 800A | 800A |
Cable Charging Current | 25A | 25A | 40A | 40A |
Line Charging Current | 5A | 5A | 5A | 5A |
Impulse Withstand Phase to Earth & Phase to Phase | 110kV | 150kV | 195kV | 200kV |
Impulse Across the Interrupter | 110kV | 150kV | 170kV | 170kV |
Power Frequency Withstand Phase to Earth ( Dry) | 50kV | 60kV | 70kV | 70kV |
Power Frequency Across the Interruptor | 50kV | 60kV | 70kV | 70kV |
Ambient Temperature | -40oC to +55oC | -40oC to +55oC | -40oC to +55oC | -40oC to +55oC |
Humidity | 0-100% | 0-100% | 0-100% | 0-100% |
Altitude | 3000m | 3000m | 3000m | 3000m |
Weight of the tank( Three Phase) | 100Kg | 109Kg | 150Kg | 150Kg |