• ADDRESS

    #42 Marcela St., Damong Maliit, Brgy. Nagkaisang Nayon, Novaliches, Quezon City 1125, Metro Manila, Philippines

  • CONTACT

     E-Mobility Department
    0939-903-9083

    Electrical and Sales Department
    0917-851-0614

    All Department
    8398-1877

    Sales Inquiry: sales [at] pesin.com.ph 

     

Distributed Automation VI – Smart Grid Automation IEC61499

August 30, 2019

Ultimately, protection devices in the field will still have some local automation, such as Autoreclosing, but the key theme of centralised automation is to provide specific signals to a central control system to make the correct decisions for re-switching the grid in adverse conditions.

 

centralised-automation-scheme.png

Figure 1 – Simplified Network Diagram of a Centralised Automation Scheme

 

Figure 1 – Simplified Network Diagram of a Centralised Automation Scheme

 

The recurrent issue in rolling out these centralised schemes is the challenge of interoperability:

“Why does x vendor’s signal y work differently to z vendors signal y?”

When all signals that are provided to the centralised automation system should be consistent across brands, the minor esotericisms of each IED can cause headaches for Protection and Control Engineers.

NOJA Power’s solution to this challenge is to build a PLC logic engine standard into the OSM Recloser RC Control System – IEC 61499. Given its flexibility in automating networks, the functionality itself has inherited the designation “Smart Grid Automation (SGA) IEC61499”.

SGA is an event-controlled automation description platform, which uses function blocks to describe automation behaviour. Users can build their own applications in SGA, install them into a NOJA Power OSM Recloser to create new functionality. SGA has access to all signals and status in the NOJA Power Recloser, providing control engineers with the capability to edit, redesign or tweak functionality to suit the local automation requirements.

For Centralised automation schemes, this capability provides tremendous flexibility in implementing signals that leave the OSM Recloser destined for the utility control room. It also provides legacy compatibility, as signals can be edited to appear the same as other network legacy equipment, shedding the shackles of enslavement to the incumbent asset base of incompatible equipment.

 

sga-logic-engine.png

Figure 2 – NOJA Power SGA IEC61499 Logic Engine UI

 

Figure 2 – NOJA Power SGA IEC61499 Logic Engine UI

SGA does not have to be confined to combining and permutating signals for the purposes of automation – it could be used to develop automation algorithms itself.

Using IP communications, SGA Algorithms can be designed to publish and subscribe to information and event flow between devices compatible with the IEC 61499 standard, whether it is a series of NOJA Power OSM Reclosers, or a mix of connected PLC and Recloser devices.

Field examples of this functionality that we have witnessed thus far include:

  • Implementing specialised Auto-Changeover Schemes between two reclosers, using a variation of controls to define the response of the algorithm beyond the standard ACO capability in the device.
  • Implementing a Ring-Mode automation scheme, (as covered in Automation IV), but with Peer to Peer communications between the tie-point recloser and midline reclosers preventing the extra close-onto-fault in system abnormal.
  • Implementing the linking of settings change between a series of devices – i.e., if Earth Fault protection is turned on at the substation, all reclosers down the feeder also have Earth Fault enabled, mitigating the risk of operator error in the repetitive task of turning on settings in multiple devices.

“IEC61499 really puts the automation power into our utility customer engineers’ hands,” reports NOJA Power Group Managing Director Neil O’Sullivan. ”Rather than requiring manufacturers to hard code new functionality, our customers have the power and ability to create their own functionality and get the most out of the automation systems.”