The FLA3.1V can communicate to a remote control via a bidirectional wireless connection. In this way all settings of the indicator can be adjusted at any time without removing the indicator from the powered line. The FLA3.1V stands out for the great flexibility of the adjustments that can be done. Beside the basic settings of the indicator like trip current, response delay, reset time, etc., the FLA3.1V can be adapted to auto-reclosers in the network. This provides for an optimized fault indication and also allows the indication of different fault types. Permanent and temporary faults can be distinguished and indicated separately.
The bidirectional connection between the remote control and the fault indicator allows to read out the present current of the monitored network with the remote control at any time.
The fault indicator type FLA3.1V can be connected to the remote indication interfaces type RIS-FR and RIS-FS. This allows an easy-to-install remote indication solution for the overhead line indicators.
The fault indicator type FLA3.1V provides two methods to detect faults. The absolute threshold detection method works with a selected fixed or an automatically calculated absolute threshold. This method can be disabled when not required.
Additionally the fault indicator type FLA3.1V provides a di/dt measurement method. This method analyses current load changes that happen within a certain amount of time. The level of load change can be adjusted.
A subsequent voltage loss is used as an additional criterion to assure correct detection of a fault. This method can also be disabled when not required.
Order Data | ||
Type FLA3.1V | | for overhead-lines | 40.46.10 |
Remote control type HS | | for indicators type FLA3.1V | 40.36.11 |
Mounting adapter | | bayonet type | 40.52.10 |
Mounting adapter | | clamp type | 40.52.11 |
Mounting adapter | | universal spline type | 40.52.12 |